PRODUCTS

LW10B-252/363 SF 6 Circuit Breaker

Description

Brief Description

Circuit breaker is used for making and breaking normal current, fault current and switching lines to realize the control and protection of power system.

Each pole of LW10B-252 circuit breaker has one break without parallel capacitor and each pole of LW10B-363 circuit breaker has double breaks with parallel capacitors. For both of products, each pole is equipped with a hydraulic operation mechanism, which can make single-pole operation and/or three-pole-gang operation.

Complete and rigorous type tests have been performed on the series products, the type test certificates were issued by Italy CESI Certification Center in 1998.

 

Main Features

1        Excellent breaking capacity with advanced construction.

2        Valve system of hydraulic mechanism can effectively prevent oil leak, and each pole is equipped with density relay to monitor SF6 leakage.

3        Good insulation performance.

4        The components and spare parts are highly interchangeable with other products of PINGGAO, experienced manufacturing technology, easy to maintain on site.

 

 

Specifications
Unit
Value
Rated voltage
kV
252
363
Rated current
A
3150/4000
Rated frequency
Hz
50/60
Rated short-time withstand current (r.m.s)
kA
50
63
Rated peak withstand current
kA
125
160
1min power frequency withstand voltage (r.m.s)
To earth/Between phases
kV
460
510
Across isolating distance
kV
460(+145)
510(+210)
Lightning impulse withstand voltage (peak)
To earth/Between phases
kV
1050
1175
Across isolating distance
kV
1050(+200)
1175(+295)
额定操作冲击耐受电压(峰值) kV
断口间
kV
 
850(+295)
极对地
kV
 
 950
Rated SF6 gas pressure(20℃)
MPa
0.4/0.6
Rated SF6 annual leakage
%
≤0.5

 

Corresponding parameter set not found, please add it in property template of background
暂未实现,敬请期待