PRODUCTS
Brief Description
LW55 Series of SF6 Dead Tank Circuit Breaker, including LW55-252, LW55-363, LW55-550 and LW55-800, are used for making and breaking normal current, fault current and switching lines to realize the control, measurement and protection of power system.
With the advantages of excellent breaking performance, reliable mechanical properties, advanced tightness technology, high design parameters, the whole structure of circuit breaker is compact, with stable and reliable performance and long endurance.
Main Features
1 The circuit breaker is of strong breaking capacity, long electrical endurance.
2 LW55 Series have excellent antiseismic and antipollution capacities, which make it suitable for those polluted places and higher elevation areas.
3 The oil pressure in hydraulic mechanism is automatic controlled and it can’t be affected by the temperature.
4 There are almost no external pipe for this new type of hydraulic operating mechanism, the possibility of oil leakage is reduced.
Technical Parameters
Specifications
|
Unit
|
Value
|
||||
Rated voltage
|
kV
|
252
|
363
|
550
|
800
|
|
Rated current
|
A
|
4000
|
5000
|
|||
Rated frequency
|
Hz
|
50/60
|
||||
Rated short-time withstand current (r.m.s)
|
kA
|
50
|
||||
Rated peak withstand current
|
kA
|
125
|
||||
1min power frequency withstand voltage (r.m.s)
|
To earth/Between phases
|
kV
|
460
|
510
|
740
|
960
|
Across isolating distance
|
kV
|
460 +(154)
|
510 +(210)
|
740 +(315)
|
960 +(460)
|
|
Lightning impulse withstand voltage (peak)
|
To earth/Between phases
|
kV
|
1050
|
1175
|
1675
|
2100
|
Across isolating distance
|
kV
|
1050 +(200)
|
1175 +(295)
|
1675 +(450)
|
2100 +(650)
|
|
Rated operating impulse withstand voltage (peak)
|
To earth/Between phases
|
kV
|
|
950
|
1300
|
1550
|
Across isolating distance
|
kV
|
|
850 +(295)
|
1175 +(450)
|
1300 +(650)
|
|
Rated SF6 gas pressure(20℃)
|
MPa
|
0.6
|
||||
Rated SF6 annual leakage
|
%
|
≤0.5
|