Stock code:600312      |                         |         

Copyright ® Henan pinggao Electric Co.,Ltd         豫ICP备05010380号

Service

Company name: henan pinggao electric co. LTD

Address: Henan province of pingdingshan city

south ring road 22

Mail editor: 467000
E -  mail : pinggao@pinggao.esgcc.com.cn

400-6700-312

If you need to consult other business, you can call the hotline directly.

General department: +86-375-3804029

Securities department: +86-375-3804064

Sales: +86-375-3803888

Customer service center: 400-6700-312

PRODUCT

>
Products_detail

PRODUCTS

JW6-126/252 type Disconnetor

Description

1.Brief Description

JW6-126/252 outdoor AC high-voltage grounding switch is for high voltage line to make the reliable grounding, in order to make sure the personal safety in the maintenance of busbar and other equipments. Equipped with CSC human mechanism(or CJ11 motor operating mechanism), the electromagnetic lock of CSC human mechanism is supplied to other equipments for electrical interlocking.

2.Main Features

2.1.Straight lun plug-in, advanced design concept, simple and reliable

2.2.The transmission shaft of products use high-quality alloy steel, hot-galvanizing process on surfaces, strong anti-corrosion. Some part of drive shaft adopt composite sleeve, good wear resistance and strong anti-corrosion.

2.3.Products has the characteristic of smooth and reliable operation, small operating force, long mechanical life, etc.

2.4.Reasonable structure, sate and reliabe performance, easy installation and commissioning on-site.

2.5. Long mechanical life: 5000 times

2.6.The transimission part of products is coated with anti-freezing greese, its operating temperature is -60°C~120°C, low temperature operation is not affected.

2.7.The contact surface of the products is Toshiba silver plating technology, the hardness of silver layer is 140HV, enhances the conductivity and wear resistance of its surface.

3.Service environment

JW6-126/252 service environment stable 1

Items

 Specifications

Unit

Value

1

The surrounding air temperature

The Highest temperature

+40

The Lowest temperature

-40

Maximum daily temperature difference

K

25

2

Altitude

m

≤2000

3

Solar radiation indensity

w/m2

1000

4

pollution class

 

Ⅲ、Ⅳ

5

Icing-thickness

mm

10

6

Wind speed

m/s

34

7

Humidity

Daily average relative humidity

%

≤95

Monthly average relative humidity

≤90

8

seismic intensity(horizontal acceleration)

m/s2

 

8 degree(0.2g)

9

The common mode voltage amplitude which is induced by the opening and closing operation of the main circuit from the auxiliary and control circuit.

kV

≤1.6

10

The installation site should be free of severe vibration and flammable, explosive materials and chemical corrosion.

4.The main technical parameters

JW6-126 Technical parameter 2

items

Specifications

Unit

Value

I

The structure and mode of earthing switch

1

Structure style

 

Straight lun plug-in

2

Operating mechanism style

 

CJ11 motor operating mechanism/CSC human mechanism

Operating mode

 

3-phase mechanical linkage

Electric or mannual

 

Electric and mannual/mannual

Motor voltage

V

AC380 or DC220/No

Control voltage

V

AC 380 or AC 220 
or DC 220 or DC 110/No

3

Backup auxiliary contact

Yes

8

II

Rated parameters

1

Rated voltage

kV

126

2

Rated frequency

Hz

50

3

Resistance of the main circuit

μΩ

≤225

4

1min power frequency withstand voltage 

kV

230

Rated lightning impulse withstand voltage peak(1.2/50ms)

kV

550

5

Rated short-time withstand current

kA

40

6

rated duration of short-circuit

s

3

7

Rated peak withstand current

kA

100

8

The switching induced current capacity of the earthing switch(A/B)

Electromagnetic induction

Reactive current

A

50/80

Induced voltage

kV

0.5/2

Breaking times

time

10

 Electrostatic induction

 

Capacity current

A

0.4/2

Induced voltage

kV

3/6

Breaking times

 time

10

9

Opening time

s

12±2

10

Closing time

s

12±2

11

Break-brake average speed

m/s

0.08

12

Closing average speed

m/s

0.08

13

mechanical life

time

≥5000

14

Assist and control circuit short-time power frequency withstand voltage

kV

2

15

radio interference voltage

μV

≤500

16

Wiring terminal static mechanical load

Longitudinal

N

1250

Horizontal

750

Vertical

1000

Safety factor

 

Static state2.75,Dynamic state1.7

17

After closing the earthing switch, the minimum air insulation distance should not less than

mm

920

18

supporting insulator

Creepage distance

mm

III grade 3150
IV grade 3906

Electric arc distance (dry)

≥900

S/P

 

≥0.9

Bending resistance

kN

≥6

4.2JW6-252Technical parameter 3

items

Specifications

Unit

Value

I

The structure and mode of earthing switch

1

Structure style

 

Straight lun plug-in

2

Operating mechanism style

 

CJ11 motor operating mechanism/CSC human mechanism

Operating mode

 

3-phase mechanical linkage

Electric or mannual

 

Electric and mannual/mannual

Motor voltage

V

AC380 or DC220/No

Control voltage

V

AC 380 or AC 220 
or DC 220 or DC 110/No

3

Backup auxiliary contact

Yes

8

II

Rated parameters

1

Rated voltage

kV

126

2

Rated frequency

Hz

50

3

Resistance of the main circuit

μΩ

≤225

4

1min power frequency withstand voltage 

kV

230

Rated lightning impulse withstand voltage peak(1.2/50ms)

kV

550

5

Rated short-time withstand current

kA

40

6

rated duration of short-circuit

s

3

7

Rated peak withstand current

kA

100

8

The switching induced current capacity of the earthing switch(A/B)

Electromagnetic induction

Reactive current

A

50/80

Induced voltage

kV

0.5/2

Breaking times

time

10

 Electrostatic induction

 

Capacity current

A

0.4/2

Induced voltage

kV

3/6

Breaking times

 time

10

9

Opening time

s

12±2

10

Closing time

s

12±2

11

Break-brake average speed

m/s

0.08

12

Closing average speed

m/s

0.08

13

mechanical life

time

≥5000

14

Assist and control circuit short-time power frequency withstand voltage

kV

2

15

radio interference voltage

μV

≤500

16

Wiring terminal static mechanical load

Longitudinal

N

1250

Horizontal

750

Vertical

1000

Safety factor

 

Static state2.75,Dynamic state1.7

17

After closing the earthing switch, the minimum air insulation distance should not less than

mm

920

18

supporting insulator

Creepage distance

mm

III grade 3150
IV grade 3906

Electric arc distance (dry)

≥900

S/P

 

≥0.9

Bending resistance

kN

≥6

 

Corresponding parameter set not found, please add it in property template of background