Name

VI012404

Summary information
Specification: Vacuum Interrupter VI012404
Affiliate classification
Description

Specification: Vacuum Interrupter VI012404

Electrical Data

Rated voltage, 50 Hz

12kV

Rated normal current

2500A

Rated short-circuit breaking current, symm.

40kA

Max. DC-component

50%

Rated short-circuit making current

100kA

Rated peak withstand current

100kA

Rated short-time withstand current, 4s

40kA

Capacitive switching acc. to GB1984
single 630A,back to back 400A

C2Class

Rated Insulation Level

Rated power-frequency withstand voltage

42/48kV

Rated lightning impulse withstand voltage

75/85kV

Thermal Data

Circuit resistance at lowest rated contact force  

≤9μΩ

Max. permitted temperature at movable stem

170ºC

Electrical Life

Breaking operations of rated short-circuit breaking current

50times

Mechanical Data

Contact stroke

8±1mm

Max. over travel

≤2mm

Maximum rebound during opening

1.2±0.2m/s

Average opening speed (0-2 mm stroke)

0.8±0.2m/s

Average closing speed (2 mm- contact making)

2m/s

Max. bouncing duration

2ms

Opening and closing non-simultaneity of three phase contacts

≤1ms

Rated added external contact final force

4400±400N

Added external contact force at contact touch point

≥3700N

Closing force due to bellows and atmosphere

240±20N

Force required to hold contacts open at full stroke

290±40N

Contact erosion limit

3mm

Mass of moving contact

2.0kg

Weight of interrupter

6.4kg

Storage life

20years

Mechanical life

20000times